California
Real Estate Inspection Association (CREIA)
Originally Adopted September 13, 1983
Revisions herein effective April 15, 1999
I. Definitions and Scope
II. Standards of Practice
Mandatory Sections:
- Foundations, Basements, and Under-floor
Areas
- Exteriors
- Roof Coverings
- Attic Areas and Roof Framing
- Plumbing
- Electrical Systems
- Heating Systems
- Central Cooling Systems
- Fireplaces and Chimneys
- Building Interior
Optional Sections:
- Other Built-in Appliances
and Systems
- Pools and Spas
III. Limitations,
Exceptions and Exclusions
I. Definitions and Scope
top
A Real Estate inspection is a non-invasive
physical examination, performed for a fee, designed to
identify material defects in the systems, structures,
and components of a building as they exist at
the time of the inspection. The specific systems,
structures and components of a building to
be examined are listed in these Standards of Practice.
B. A material defect is a condition
that significantly affects the value, desirability, habitability,
or safety of the building. Style or aesthetics shall
not be considered in determining whether a specific system,
structure, or component is defective.
C. These Standards provide inspection
guidelines, make public the services provided by private fee-paid
inspectors, and define certain terms relating to these
inspections.
D. Sections 1 through 10 of these Standards
are a mandatory part of all such inspections. Sections
11 through 12 are optional.
E. Unless otherwise agreed between the inspector
and client, these Standards shall apply to the primary building
and its associated primary parking structure. The inspection
shall be limited to those specific systems, structures
and components that are present and visually accessible.
Components and systems shall be operated
with normal user controls only and as conditions
permit. Inspections performed in accordance with these
Standards are not intended to be technically exhaustive.
F. Inspection reports shall describe
and identify in written format the inspected systems,
structures, and components of the building
and shall identify material defects.
G. Inspection reports may contain recommendations
regarding conditions reported or recommendations for
further evaluation by appropriate persons.
II. Standards of Practice
SECTION 1 - Foundations, Basements,
and Under-floor Areas
top
A. Items to be identified and reported:
1. Foundation and other support components.
2. Under-floor ventilation.
3. Location of under-floor access
opening(s).
4. Wood separation from soil.
5. Presence of drainage systems or
sump pumps within foundation footprint.
6. Presence or absence of seismic anchoring
and bracing components.
B. The inspector is not required to:
1. Enter under-floor areas that are
not accessible or where entry could cause damage
or pose a hazard to the inspector.
2. Move stored items, vegetation or debris,
or perform any excavations or other intrusive testing
to gain access.
3. Operate or evaluate adequacy
of sump pumps or drainage systems.
4. Identify size, spacing, location
or adequacy of foundation bolting and bracing components
or reinforcement systems.
5. Perform any intrusive examination
or testing, or use any special equipment such as,
but not limited to, levels, probes or meters.
SECTION 2 - Exteriors
top
A. Items to be identified and reported:
1. Surface grade, hardscaping and drainage
within six feet of the inspected building or associated
primary parking structure.
2. Wall cladding, veneers, flashing, trim,
eaves, soffits and fascias.
3. Exterior portions of a representative
sampling of doors and windows.
4. Attached decks, porches, balconies, stairs,
columns, walkways, guard-rails and handrails.
B. The inspector is not required to:
1. Operate or evaluate any
mechanical, electro-mechanical, or underground drainage
systems.
2. Operate or evaluate storm
windows, storm doors, screening, shutters or awnings.
3. Operate or evaluate remote-control
devices.
4. Examine detached buildings and
structures (other than the primary parking structure),
patio enclosures, fences, and retaining walls.
5. Examine items not visible from
a readily accessible walking surface.
SECTION 3 - Roof Coverings
top
A. Items to be identified and reported:
1. Roof coverings.
2. Flashing, vents, skylights and
other penetrations.
3. Roof drainage systems.
B. The inspector is not required to:
1. Walk on the roof surface if, in the opinion
of the inspector, there is a possibility of damage to the
surface or a hazard to the inspector.
2. Perform a water test, warrant or certify
against roof leakage or predict life expectancy.
SECTION 4 - Attic Areas and Roof
Framing
top
A. Items to be identified and reported:
1. Framing and sheathing.
2. Access opening(s) and accessibility.
3. Insulation material(s).
4. Ventilation.
B. The inspector is not required to:
1. Enter attic areas that, in the
opinion of the inspector, are not accessible or where
entry could cause damage.
2. Remove insulation materials or identify
composition or "R" value of insulation material.
3. Activate thermostatically operated fans.
SECTION 5 - Plumbing
top
A. Items to be identified and reported:
1. Supply, waste, and vent piping.
2. Fixtures, faucets and drains.
3. Water heating equipment, including combustion
air, venting, connections, energy sources, seismic bracing,
and temperature-pressure relief valves.
4. Functional flow of water
supply and functional drainage at fixtures.
5. Gas piping and connectors.
6. Cross-connections.
B. The inspector is not required to:
1. Operate any valve other than
fixture faucets and hose faucets attached to the building.
2. Operate any system, fixture
or component which is shut down or disconnected.
3. Examine or verify operation of water supply or pressure assistance
systems, including, but not limited to:
wells, pumps, tanks, and related equipment.
4. Verify functional flow or pressure
at any fixture or faucet where the flow end is capped
or connected to an appliance, or measure pressure,
volume or temperature.
5. Examine or operate any sewage
disposal system or component including, but not limited
to: septic tanks and/or any underground
system or portion thereof, or ejector pumps for rain
or waste.
6. Examine the overflow device of
any fixture.
7. Evaluate the potability of water,
compliance with local or state conservation or energy standards,
or proper design or sizing of any water, waste, and venting
components, fixtures, or piping.
8. Identify whether water supply and waste
disposal systems are public or private.
9. Evaluate time to obtain hot water
at fixtures, or perform testing of any kind to water heater
elements.
10. Examine ancillary systems or
components such as, but not limited to: those relating to solar water heating, hot
water circulation, yard sprinklers, water conditioning,
swimming pools or spas and related equipment, and fire sprinklers.
11. Test shower pans for leakage or fill
any fixture with water during examination.
12. Evaluate the gas supply system
for leaks or pressure.
13. Determine effectiveness of anti-siphon,
back-flow prevention, or drain-stop devices.
14. Determine whether there are sufficient
clean-outs for effective clearing of drains.
15. Evaluate gas, liquid propane,
or oil storage tanks.
SECTION 6 - Electrical Systems
top
A. Items to be identified and reported:
1. Service conductors, equipment,
and capacity.
2. Panels and overcurrent protection
devices.
3. Service and equipment grounding.
4. Wiring types and methods.
5. A representative sampling
of switches, receptacles, and light fixtures.
6. Ground-fault circuit-interrupters.
B. The inspector is not required to:
1. Operate electrical systems
or components which are disconnected or shut
down.
2. Disconnect any energized system or
appliance.
3. Remove deadfront covers where not accessible,
or if removal could cause injury or damage to persons or
property, or remove device cover plates.
4. Operate overcurrent protection
devices, or evaluate compatibility of overcurrent
protection devices with the panelboard manufacturer.
5. Examine or test smoke detectors.
6. Operate ground-fault circuit-interrupter
devices by other than the manufacturer’s test button.
7. Examine de-icing equipment, or
private or emergency electrical supply sources, including
but not limited to: generators, windmills, photovoltaic
solar collectors, or battery or electrical storage facilities.
SECTION 7 - Heating Systems
top
A. Items to be identified and reported:
1. Heating equipment and operation using
normal user controls.
2. Venting systems.
3. Combustion and ventilating air.
4. Energy source and connections.
5. Heating distribution system(s)
including a representative sampling of ducting, duct
insulation, outlets, radiators, piping systems and
valves.
B. The inspector is not required to:
1. Examine
or evaluate condition of heat exchangers.
2. Determine uniformity, temperature,
airflow or balance of heat supply to any room or building,
or examine for warming at any heating system
distribution component when access would require
steps or a ladder, or determine leakage in any ductwork.
3. Examine electric heater elements
or heat pump fluid/gas materials, or examine below
ground/slab systems, ducts, fuel tanks and related
components.
4. Determine or examine thermostat
calibration, heat anticipation, or automatic setbacks or
clocks.
5. Examine radiant or geothermal
heat pump systems.
6. Examine any solar-energy heating
systems or components.
7. Examine electronic air filtering
systems.
8. Operate heat pump systems
when the ambient air temperature may damage the equipment,
or operate any heat pump system in "emergency"
heat mode.
9. Examine humidity control systems
and components.
SECTION 8 - Central Cooling Systems
top
A. Items to be identified and reported:
1. Cooling equipment and operation using
normal user controls.
2. Cooling distribution system(s)
including a representative sampling of ducting, duct
insulation, outlets, piping systems and valves.
3. Energy source and connections.
4. Condensate drains.
B. The inspector is not required to:
1. Determine uniformity, temperature,
airflow or balance of cool air supply to any room or building,
or examine for cooling at any cooling system
distribution component when access would require
steps or a ladder, or determine leakage in any ductwork.
2. Examine electrical current, coolant
fluids or gases, or coolant leakage.
3. Examine electronic filtering systems.
4. Determine or examine thermostat
calibration, cooling anticipation, or automatic setbacks
or clocks.
5. Examine any non-central cooling
unit(s) or gas-fired, solar or geothermal cooling system
or food, wine or similar storage cooling system.
6. Examine humidity control systems
and components.
SECTION 9 - Fireplaces and Chimneys
top
A. Items to be identified and reported:
1. Chimneys, flues, dampers and associated
components.
2. Fireboxes, hearth extensions and permanently
installed accessory components.
3. Manufactured solid-fuel or gas-burning
appliances.
B. The inspector is not required to:
1. Determine adequacy of draft,
perform a smoke test, or dismantle or remove any
component.
2. Examine the structural integrity
of fireplaces and chimneys.
3. Examine or operate ancillary
or non-permanently installed components.
SECTION 10 - Building Interior
top
A. Items to be identified and reported:
1. Walls, ceilings and floors.
2. Security bars, ventilation components,
and a representative sampling of doors and windows.
3. Stairs, handrails, and guardrails.
4. Permanently installed cabinet
and countertop surfaces.
5. Safety glazing in locations subject to
human impact.
B The inspector is not required to:
1. Operate or evaluate security
bar release and opening mechanisms, whether interior or
exterior, including compliance with local, state, or federal
standards.
2. Determine whether a building
is secure from forcible or unauthorized entry.
3. Evaluate the condition
of floor, wall or ceiling finishes or coverings, or other
surfaces for other than evidence of moisture damage.
4. Examine window or door coverings
or treatments.
5. Evaluate fastening of countertops,
furniture or cabinets supported by floors, ceilings and/or
walls.
6. Evaluate separation walls, ceilings,
and floors, including, but not limited to, the fire- resistivity
or acoustical characteristics, between dwelling units.
7. Examine the interior concrete
slab-on-grade when concealed by any floor coverings.
8. Operate or evaluate safety
features of any garage door opener unless included as an
inspection option per Section 11.
SECTION 11
(OPTIONAL) - Other Built-In Appliances and
Systems
top
The inspector may examine any
of the following at his/her discretion, as agreed with client:
Attic power vents, central vacuum, cook-tops and
exhaust fans, dishwashers, food waste disposers, garage door openers,
hydrotherapy tubs, ovens, microwave ovens, refrigerators,
freezers, trash compactors, or whole-house fans.
A. Items to be identified and reported:
1. Optional systems,
components and appliances specifically examined
during the inspection.
2. Basic operation of optional systems,
components and appliances specifically included
in the inspection.
B. The inspector is not required to:
1. Activate any system or appliance
that is shut down.
2. Operate or evaluate any
system, component, or appliance that does
not respond to normal user controls.
3. Operate any gas appliance that
requires the use of a match or other remote burner lighting
device.
4. Operate any system or
appliance that requires the use of special codes,
keys, combinations, or devices.
5. Operate any system, component,
or appliance where damage may occur.
6. Determine thermostat(s) calibration,
adequacy of heating elements, operate or evaluate
self-cleaning oven cycles, signal lights, or automatic
setbacks or clocks.
7. Determine leakage from microwave
ovens.
8. Determine the presence or operation
of backdraft damper devices in exhaust devices.
9. Examine any sauna, steam-jenny,
kiln, clothes washing or drying machine, toaster, ice-maker,
coffee-maker, can-opener, bread-warmer, blender, instant
hot water dispenser, or any other similar small, ancillary
or non-built-in appliances.
SECTION 12 (OPTIONAL) - Pools and Spas
top
The inspector may examine the
following at his/her discretion, as agreed with client:
A. Items to be identified and reported:
1. Location and type of pool or spa examined.
2. Conditions limiting or otherwise
inhibiting inspection.
3. Enclosure and related gates.
4. Hardscaping and drainage related to the
inspected pool or spa.
5. Condition of visible portions
of systems, structures, or components.
6. Normally necessary and present equipment
such as: lights, pumps, heaters, filters, and related mechanical
and electrical connections.
B. The inspector is not required to:
1. Examine any above-ground, movable,
freestanding or otherwise non-permanently installed pool
or spa, or self-contained equipment.
2. Come into contact with pool or spa water
to examine the system, structure, or
components.
3. Determine adequacy of spa jet water force
or bubble effect.
4. Determine structural integrity
or leakage of any kind.
5. Evaluate thermostat(s) or their
calibration, heating elements, chemical dispensers, water
chemistry or conditioning devices, low voltage or computer
controls, timers, sweeps or cleaners, pool or spa covers
and related components.
6. Operate or evaluate filter
backwash systems.
7. Examine accessories, such as,
but not limited to: aerators or air-blowers, diving or jump
boards, ladders, skimmers, slides or steps.
III. LIMITATIONS,
EXCEPTIONS AND EXCLUSIONS
top
*Note: All limitations, exceptions and exclusions
apply equally to mandatory and optional Sections.
A. The inspector may exclude from the
inspection any system, structure, or component
of the building which is inaccessible, concealed
from view, or cannot be inspected due to circumstances
beyond the control of the inspector, or which
the client has agreed is not to be inspected. If an inspector
excludes any specific system, structure, or component
of the building from the inspection, the inspector
shall confirm in the report such specific system,
structure, or component
of the building not inspected
and the reason(s) for such exclusion(s).
B. The inspector may limit the inspection
to individual specific systems, structures, or components
of the building. In such event, the inspector
shall confirm in the report that the inspection
has been limited to such individual specific systems,
structures, and components of the building.
C. The following are excluded from the scope
of a real estate inspection unless specifically agreed
otherwise between the inspector and the client:
1. Systems, structures, or components
not specifically identified in these Standards.
2. Environmental hazards or conditions, including,
but not limited to, toxic, reactive, combustible, corrosive
contaminants, wildfire, geologic or flood.
3. Examination of conditions
related to animals, rodents, insects, wood-destroying insects,
organisms, mold, and mildew.
4. Geotechnical, engineering, structural,
architectural, geological, hydrological, land surveying
or soils-related examinations.
5. Certain factors relating to any systems,
structures, or components of the building,
including, but not limited to: adequacy, efficiency, durability
or remaining useful life, costs to repair, replace or operate,
fair market value, marketability, quality, or advisability
of purchase.
6. Systems, structures, or components,
of the building which are not permanently installed.
7. Determination of compliance with
installation guidelines, manufacturers’ specifications,
building codes, ordinances, regulations, covenants, or other
restrictions, including local interpretations thereof.
8. Common areas, or systems, structures,
or components thereof, including, but not limited
to, those of a common interest development as defined in
California Civil Code Section 1351 et seq.
D. The inspector is not required to perform
any of the following as part of a real estate inspection:
1. Move any personal items or other obstruction(s)
such as, but not limited to:
furniture, floor or wall coverings, window coverings, snow,
ice, water, debris, and foliage which may obstruct visibility
or access.
2. Determine causes for the need of repair
or replacement, or specify repair or replacement procedures
or materials.
3. Determine existence of latent deficiencies
or defects.
4. Dismantle any system, structure,
or component, or perform any intrusive or
destructive examination, test or analysis.
5. Obtain or review information from any
third-parties including, but not limited to: government
agencies (such as permits), component or system
manufacturers (including product defects, recalls or similar
notices), contractors, managers, sellers, occupants, neighbors,
consultants, homeowner or similar associations, attorneys,
agents or brokers.
6. Activate or operate any system
or component that is shut down or does not respond
to normal user controls, nor access any area
or operate any component or system
which may jeopardize the safety of the inspector,
or any other person or thing.
7. Research the history of a property,
report on its potential for alteration, modification,
extendibility, or its suitability for a specific or proposed
use or occupancy.
8. Offer any form of guarantee or warranty.
9. Examine or evaluate the
acoustical or other nuisance characteristics of any system,
structure, or component of a building,
complex, adjoining properties, or neighborhood.
10. Operate or evaluate any
recreational system, structure or component.
11. Operate or evaluate low
voltage electrical (less than single-phase line voltage,
typically 120-volts), antennas, security systems,
cable or satellite television, telephone, remote controls,
radio controls, timers, intercoms, computers, photo-electric,
motion sensing, or other such similar non-primary electrical
power devices, components, or systems.
12. Use any special equipment to
examine any system, structure, or component
of a building.
13. Probe or exert pressure on any component,
system or structure.
14. Examine or evaluate fire-resistive
qualities of any system, structure or component
of the building.
15. Examine every individual component
of a system or structure, where such components
are typically replicated, including, but not limited to:
doors, windows, switches and receptacles. A representative
sampling may be performed in order to examine
such systems, structures, or components of
a building.
16. Determine the age of construction
or installation of any system, structure,
or component of a building, or differentiate
between original construction or subsequent additions, improvements,
renovations or replacements thereto.
|